IN HOUSE TEST REPORT
Upvc pipe size: Diameter 225 MM PN 10 S/W
Date: 25/09/2026
B.NO: 20251230-M8-B-12
D. N. NO: 33333
| Test |
BSEN 1452 test Requirements. |
Test Results |
| Mean Outside Diameter(mm) |
Min: 225.0 Max: 225.70 |
Mean : 225.34 |
| Wall Thickness |
Min: 8.60 Max: 9.70 |
Min: 8.71 Max: 9.12 |
| Length |
Meters Min: 6.0 |
6.0 |
| Tensile Strength |
ISO: 6259 ≥ 45 Mpa. |
47.47 |
| Elongation @ Break |
ISO: 6259 ≥ 80 % |
88.12 |
| Resistance to Acetone ( ISO : 3472) |
No Delimitation or Disintegration Should Occur - 2 hours |
NO DELAMINATION |
| VICAT SOFTENING POINT (ISO:2507) |
MIN : 79 Deg. C |
84.27 |
| OPACITY( ISO: 7686) |
LIGHT PASSING SHALL NOT MORE THAN 0.2% |
0.01% |
| DENSITY TEST (1183-1,2) |
MIN: 1360KG/M3 MAX: 1450 KG/M3 |
1,429 |
| Heat Reversion Test : (%) ISO: 2505 |
Change in length should not more than 5% |
-3.35% |
| HYDROSTATIC PRESSURE TEST: (ISO: 1167-1,2) |
PIPE SHOULD WITHSTAND 34 BARS PRESSURE FOR 1HOUR AS PER PRESSURE TEST CALCULATION. |
PIPE WITHSTOOD 35 BARS PRESSURE FOR 1 HOUR |
| Impact Resistance( ISO: 3127) |
TRUE IMPACT RATE SHALL NOT BE MORETHAN 10% |
TIR BELOW 10% (0/25 PASSED) |
Test Assessment: The pipe sample 225 mm PN- 10 S/W tested as per BSEN: 1452.
The sample meets all requirements as per the Standards.
VICAT SOFTENING TEMPERATURE TEST
TESTING STANDARD: BSEN 1452-2
TEST METHOD: AS PER ISO: 2507
U-PVC PIPE SAMPLE SIZE AND CLASS: 225 MM PN 10 (8.60 MM W.T) B.NO: 20251230-M8-B-12
NUMBER OF SAMPLES : 3
TEST REQUIREMENTS : VICAT SOFTENING TEMPERATURE SHOULD NOT BE LESS THAN 79 DEG.C
SAMPLE 1 : 84.86 Deg.C
SAMPLE 2: 83.90 Deg.C
SAMPLE 3: 84.06 Deg.C
AVERAGE : 84.27 Deg.C
TEST ASSESSMENT: SAMPLE PASSED
OPACITY TEST
TESTING STANDARD: BSEN 1452-2
TEST METHOD: AS PER ISO: 7686
U-PVC PIPE SAMPLE SIZE AND CLASS: 225 MM PN 10 (8.60 MM W.T) B.NO: 20251230-M8-B-12
SAMPLE SIZE: 45 MM X 45 MM
NUMBER OF SAMPLES : 2
TEST REQUIREMENTS : MAXIMUM LIGHT PASSING : 0.20%
SAMPLE 1: 0.01%
SAMPLE 2: 0.00%
AVERAGE : 0.01%
TEST ASSESSMENT: SAMPLE PASSED
DENSITY TEST
TESTING STANDARD: BSEN 1452-2
TEST METHOD: AS PER ISO: 1183-1
U-PVC PIPE SAMPLE SIZE AND CLASS: 225 MM PN 10 (8.60 MM W.T) B.NO: 20251230-M8-B-12
NUMBER OF SAMPLES : 3
TEST REQUIREMENTS : MINIMUM: 1,360 Kg/m3 MAXIMUM : 1,450 Kg/m3
SAMPLE 1: 1,430 Kg/m3
SAMPLE 2: 1,422 Kg/m3
SAMPLE 3: 1,435 Kg/m3
AVERAGE DENSITY : 1,429 Kg/m3
TEST ASSESSMENT: SAMPLE PASSED
REVERSION TEST
TESTING STANDARD: BSEN 1452-2
TEST METHOD: AS PER ISO: 2507
U-PVC PIPE SAMPLE SIZE AND CLASS: 225 MM PN 10 (8.60 MM W.T) B.NO: 20251230-M8-B-12
NUMBER OF SAMPLES : 3
TEST REQUIREMENTS : CHANGE IN LENGTH SHOULD NOT ALTERED MORETHAN 5%
SAMPLE 1 : -3.52 %
SAMPLE 2: -3.52 %
SAMPLE 3: -3.01%
AVERAGE SHRINKAGE : -3.35 %
TEST ASSESSMENT: SAMPLE PASSED
IN HOUSE LAB TESTING DOCUMENTS
HYDROSTATIC PRESSURE TEST ( AS PER ISO: 1167-1,2)
TEST STANDARD SPECIFICATION: BSEN 1452-2
UPVC PIPE SAMPLE SIZE : 225 MM PN 10 ( 8.60 MM W.T) B.NO : 20251230-M8-B-12
TEST CONDITIONS: MINIMUM TIME FRAME : 1 hour @ 20 Deg.C
TEST REQUIREMENTS: Pipe Should withstand 34.40 Bars as per the pressure test calculation. During the test pipe without Burst and shape change .
TEST RESULT : Pipe sample withstood 34.9 Bar Pressure for 1 hour without Burst.
REMARKS : SAMPLE PASSED .
IN HOUSE LAB TESTING DOCUMENTS
IMPACT TEST ( AS PER ISO: 3127 ) Round -Clock Method
TEST STANDARD SPECIFICATION: BSEN 1452-2
TEST REQUIREMENTS : TIR BELOW 10% ( TRUE IMPACT RATE)
UPVC PIPE SAMPLE SIZE AND CLASS : 225 MM PN 10 ( 8.60 MM W.T)
BATCH NUMBER : 20251230-M8-B-12 SIZE OF THE SAMPLE : 200 MM (+/- 10 MM) LONG
NUMBER OF SAMPLES USED : 3 NUMBER OF STROKES : 25 NUMBER OF FAILURES : 0/25
MASS FALLING HEIGHT : 1.81 METERS FALLING WEIGHT ( IN KGS ) : 2.49 kgs
CONDITION OF SAMPLE @ : @ 0 Deg.C DIMENSION FOR THE NOSE OF THE STRIKER - D 90
TEST RESULTS : TIR BELOW 10%
REMARKS : SAMPLE PASSED .
UPVC PIPE PHYSICAL DIMENSIONS CHART.
Item: UPVC PIPE : SIZE : 225 MM PN 10 (8.60 MM W.T) .
D.O.M: 30.12.2025 BATCH NUMBER : 20251230-M8-B-12
STANDARD AS PER BSEN 1452
| S.NO |
REQUIREMENTS WALL THICKNESS OF THE PIPE ( MM ) MINIMUM: 8.60 MM MAXIMUM : 9.70 MM |
REQUIREMENTS OUTSIDE DIAMETER OF THE PIPE (MM) MINIMUM: 225.00 MM MAXIMUM: 225.70 MM |
COMPLY / NOT COMPLY |
| READING 1 (MM) |
READING 2 (MM) |
MEAN WALL THICKNESS (MM) |
STATUS |
AVERAGE OD (MM) |
STATUS |
| 1 |
8.79 |
9.09 |
8.94 |
COMPLY |
225.34 |
COMPLY |
COMPLIED |
| 2 |
8.74 |
8.95 |
8.85 |
COMPLY |
225.29 |
COMPLY |
COMPLIED |
| 3 |
8.71 |
8.93 |
8.82 |
COMPLY |
225.35 |
COMPLY |
COMPLIED |
| 4 |
8.86 |
8.87 |
8.87 |
COMPLY |
225.44 |
COMPLY |
COMPLIED |
| 5 |
8.80 |
9.03 |
8.92 |
COMPLY |
225.38 |
COMPLY |
COMPLIED |
| 6 |
8.75 |
9.09 |
8.92 |
COMPLY |
225.21 |
COMPLY |
COMPLIED |
| 7 |
8.78 |
8.88 |
8.83 |
COMPLY |
225.44 |
COMPLY |
COMPLIED |
| 8 |
8.81 |
9.12 |
8.97 |
COMPLY |
225.39 |
COMPLY |
COMPLIED |
| 9 |
8.76 |
8.97 |
8.87 |
COMPLY |
225.28 |
COMPLY |
COMPLIED |
| 10 |
8.80 |
9.00 |
8.90 |
COMPLY |
225.23 |
COMPLY |
COMPLIED |
IN HOUSE LAB TESTING DOCUMENTS
UPVC PIPE TENSILE STRENGTH TEST ( AS PER ISO: 6259 )
TEST STANDARD SPECIFICATION : BSEN 1452-2
UPVC PIPE SAMPLE SIZE: 225 MM PN 10 ( 8.60 MM W.T) B.NO : 20251230-M8-B-12
NUMBER OF SAMPLES STRIPES : 5 TEST SPEED : 5 MM +/- 1 MM (PER MINUTE)
TEST REQUIREMENTS FOR UPVC PIPE SAMPLE: MINIMUM 45 Mpa
NUMBER OF SAMPLE TESTED : 5 NUMBERS
| SAMPLE |
WALL THICKNESS (MM) |
WIDTH (MM) |
VALUE (IN Mpa) |
| SAMPLE NO 1 : |
8.82 |
6.0 |
47.30 |
| SAMPLE NO 2 : |
8.85 |
6.0 |
47.30 |
| SAMPLE NO 3 : |
8.87 |
6.0 |
47.22 |
| SAMPLE NO 4 : |
8.82 |
6.0 |
47.59 |
| SAMPLE NO 5 : |
8.92 |
6.0 |
47.95 |
TEST RESULT : AVERAGE TENSILE STRESS VALUE : 47.47 Mpa
REMARKS : SAMPLE PASSED .
ACETONE TEST
TESTING SPECIFICATION STANDARD: BSEN 1452-2
TEST METHOD: AS PER ISO: 3472
U-PVC PIPE SAMPLE SIZE AND CLASS : 225 MM PN 10 ( 8.60 MM W.T) B.NO: 20251230-M8-B-12
SAMPLE SIZE: 100 MM LONG X 25 MM WIDTH
NUMBER OF SAMPLES : 3
TEST REQUIREMENTS : NO DELAMINATION AND INTEGRATION
SAMPLE 1: NO DELAMINATION
SAMPLE 2: NO DELAMINATION
SAMPLE 3 : NO DELAMINATION
TEST ASSESSMENT: NO DELAMINATION , SAMPLE PASSED
IN HOUSE LAB TESTING DOCUMENTS
UPVC PIPE ELONGATION TEST ( AS PER ISO: 6259 )
TEST STANDARD SPECIFICATION: BSEN 1452-2
UPVC PIPE SAMPLE SIZE: 225 MM PN 10 ( 8.60 MM W.T) B.NO : 20251230-M8-B-12
NUMBER OF SAMPLES STRIPES : 5 TEST SPEED : 5 MM +/- 1 MM (PER MINUTE)
TEST REQUIREMENTS FOR UPVC PIPE SAMPLE : MINIMUM 80 %
NUMBER OF SAMPLE TESTED : 5 NUMBERS
| SAMPLE |
WALL THICKNESS (MM) |
WIDTH (MM) |
VALUE ( IN % ) |
| SAMPLE NO 1 : |
8.72 |
6.0 |
89.50 |
| SAMPLE NO 2 : |
8.85 |
6.0 |
87.67 |
| SAMPLE NO 3 : |
8.85 |
6.0 |
88.96 |
| SAMPLE NO 4 : |
8.79 |
6.0 |
87.21 |
| SAMPLE NO 5 : |
8.84 |
6.0 |
87.28 |
TEST RESULT : AVERAGE ELONGATION : 88.12 %
REMARKS : SAMPLE PASSED .